Error 9016 · CNC 8058 / 8060 / 8065 · CNC 8070 · CNCelite 8058 / 8060 / 8065 / 8070
Message: Resource out of the permitted range.
Detection
While compiling the PLC program.
Cause
Any programmed resource is out of the permitted range.
Solution
The valid range for each resource is the following.
- Inputs (I1-I1024).• Outputs (O1-O1024).• Local inputs (LI1-LI16).• Local outputs (LO1-LO8).• Marks (M1-M8192).• Messages (MSG1-MSG1024).• Errors (ERR1-ERR1024)• Clocks (CLK).• Registers (R1-R1024).• Register bits (B0-B31 R1-R1024).• Timer status (T1-T512).• Counter status (C1-C256).