Error 5060 · CNCelite 8058 / 8060 / 8065 / 8070
Message: Read function not supported for the variable.
Detection
During execution.
Cause
The possible causes are:
- The variable does not have read permission from the PLC.
- It is not allowed to read the variable using this function.
Solution
The variable must have read permission from the PLC. If the variable has a numeric value, use cncrd. If the variable has a text, use cncrd_txt.