Error 0072 · CNCelite 8058 / 8060 / 8065 / 8070
Message: Feedback alarm not activated.
Detection
During the validation of the machine parameters.
Cause
In some set of parameters of an analog axis or spindle, the feedback alarm is not activated. This situation can only be allowed during setup; once setup is completed, this watch must be enabled.
Solution
Activate the feedback alarm in all the sets of the analog axes and spindles (parameter FBACKAL).
8058 80608065 8070 ꞏ12ꞏ